How often am I supposed to get my cleanroom validated?
ISO 14644-2 specifies that a cleanroom that is ISO class 5 or cleaner needs to have their testing procedures done every 6 months. For any cleanrooms less stringent (class 6 through 9) it is only necessary once per year.
Strategic Testing: (Table 1) Schedule of Tests to Demonstrate Continuing Compliance.
Test Parameter | Class | Maximum Time Interval | Test Procedure |
Particle Count Test | < or = ISO 5 | 6 Months | ISO 14644-1 Annex A |
> ISO 5 | 12 Months | ||
Air Pressure Difference | All Classes | 12 Months | ISO 14644-1 Annex B5 |
Airflow | All Classes | 12 Months | ISO 14644-1 Annex B4 |
|
Test Parameter | Class | Maximum Time Interval | Test Procedure |
Installed Filter Leakage | All Classes | 24 Months | ISO 14644-3 Annex B6 |
Containment Leakage | All Classes | 24 Months | ISO 14644-3 Annex B4 |
Recovery | All Classes | 24 Months | ISO 14644-3 Annex B13 |
Airflow Visualization |
All Classes | 24 Months | ISO 14644-3 Annex B7 |