How often am I supposed to get my cleanroom validated?

Time Published February 2, 2012 by Renzo

ISO 14644-2 specifies that a cleanroom that is ISO class 5 or cleaner needs to have their testing procedures done every 6 months. For any cleanrooms less stringent (class 6 through 9) it is only necessary once per year.


Strategic Testing: (Table 1) Schedule of Tests to Demonstrate Continuing Compliance.

Test Parameter Class Maximum Time Interval Test Procedure
Particle Count Test < or = ISO 5 6 Months ISO 14644-1 Annex A
> ISO 5 12 Months
Air Pressure Difference All Classes 12 Months ISO 14644-1 Annex B5
Airflow All Classes 12 Months ISO 14644-1 Annex B4


Strategic Testing: (Table 2) Schedule of Additional Optional Tests.

Test Parameter Class Maximum Time Interval Test Procedure
Installed Filter Leakage All Classes 24 Months ISO 14644-3 Annex B6
Containment Leakage All Classes 24 Months ISO 14644-3 Annex B4
Recovery All Classes 24 Months ISO 14644-3 Annex B13
Airflow
Visualization
All Classes 24 Months ISO 14644-3 Annex B7